Final Exam Tutorial Session Problems and Solutions Summer 2023

First-page document preview for Final Exam Tutorial Session Problems and Solutions Summer 2023 in ELE 637: Energy Conversion at Toronto Metropolitan University (TMU). Inspect the first page below or request the complete PDF study document for free.

Independent study archive Learn more

Materials are uploaded by users for self-study purposes. PwnHero is an independent platform, not affiliated with, sponsored by, or endorsed by any university or institution.

📄 Page 1 Preview
First page preview of Final Exam Tutorial Session Problems and Solutions Summer 2023 for Energy Conversion at Toronto Metropolitan University (TMU)

Page 1 Key Topics & Excerpt

🔍 Text Transcript

First page excerpt for quick study reference. Complete formulas, diagrams, and subsequent pages are available in the full document.

PwnHero Tutorial Session - Final Exam ELE637: Energy Conversion Summer 2023 1- A 400-MVA, 240-kV/24-KV, three-phase Y- Δ transformer has an equivalent series impedance of 1.2 + j6 - per phase referred to the high-voltage side. The transformer is supplying a three-phase load of 400 MVA, 0.8 power factor lagging at a terminal voltage of 24 kV (line to line) on its low-voltage side. The primary is supplied from a feeder with an impedance of 0.6 + j1.2 - per phase. Determine the line-to-line voltage at the high-voltage terminals of the transformer and the sending-end of the feeder. 2-A Δ-Y connected bank of three identical 100-kVA, 2400-V/120-V, 60-Hz transformers is supplied with power through a feeder whose impedance is 0.065 + j0.870 Ω per phase. The equivalent series impedance of each 1φ transformer referred to the low-voltage side is 0.0012+j0.003 Ω. The voltage at the sending end of the feeder is held constant at 2400 V line-to-line. The load can be modeled as three equal impedances connected in Δ from. Each phase impedance ZL is equal to 0.410+j0.135 Ω. Determine: (a) The load line-to-line voltage, (b) The transformer windings currents, (c) The efficiency (ignore the core losses but consider the feeder losses). 3- The magnetization characteristic of a DC generator running at 1000 rpm is shown below. This machine has armature resistance of 0.5 Ω and field resistance of 100 Ω. The machine is driven as a shunt DC generator by a diesel engine and is connected to a load of 5 Ω. The engine speed is adjustable. The generator is required to deliver 2kW to the load, calculate: (a) Output voltage of the DC machine. (b) Field current and armature current of the machine. (c) EMF of DC machine and speed of diesel generator. PwnHero.com

Related ELE Courses at Toronto Metropolitan University (TMU)